NOTICE INVITING
e-TENDERS
etender.punjabgovt.gov.in
Directorate, Animal Husbandry, Punjab 17-Bays
Building,Sector-17,Chandigarh.
e-Tender/Notice-10/ 2015-16
The Department of Animal Husbandry, Punjab 17-Bays Building,
Sector-17,Chandigarh, invites e-tender on double bid system for
the expression of interest from the reputed agencies/contractors for
supply, installation and commissioning of complete environmental
control system with clean room works including validation (HVAC)
for Quality control Lab (approved plan/ BOQ) as per GMP standards at
Punjab Veterinary Vaccine Institute, Ludhiana, Punjab. For
additional details such as detailed specifications, important dates
etc visit the website: etender.punjabgovt.gov.in.Tender form,
specifications, terms and condition can be obtained from this
website on payment of Rs. 20/-(online payment) as per e-tendering
procedure. Other details/brief description of the work can be seen
in the office of the Deputy Director, Animal Husbandry, I/c Punjab
Veterinary Vaccine Institute, PAU Campus, Ludhiana .The tender will
be in double bid system i.e. Technical/Pre-qualification Bids and
Financial/Commercial Bids.
1.
Complete profile of the Authorized /Registered firm along
with organizational structure, Key personnel employed along with
their educational qualification and experience.
2.
The intending firms should have satisfactorily completed two
similar type of quoted work related to Vaccine Production/
/Quality Control/ Animal House during the last ten years. The firm
who executed the work of more than 75% of the project cost will be
eligible . At least one same nature work completed should be of
Central/State Government Organization /Central autonomous
bodies/Central Public Sector undertaking.
3.
The completion performance certificate for the similar
completed work duly issued by the competent authority/Head of the
Institution.
4.
Minimum solvency equal to the 50% at the project cost.
5.
The bidder should have minimum turnover 4 times of the
project cost considering during last five years.
6.
Undertaking that the bidder will invest minimum 25% of the
contract value of work own his own.
7.
Tenderers should submit complete power point presentation on
the organization, experience of work, man power with financial
details.
8.
Tenderers will provide complete validation of the system. It
could include design qualifications, installation qualifications,
performance and operational qualifications.
9.
Design documentation need to be approved by the competent
authority .
10.
Third party validation is to be organized by the tenderer.
11.
The bidder must enclose attested copies/ proof of consisting,
Pan Card, TIN No., Vat No., Service Tax No., CST, EPE,
Registration/Authorization of the Firm etc.
12.
The bidder firm should not be black listed/debarred by any
department/ Organization.
13.
Bidder must submit undertaking in the shape of affidavit
regarding providing all the information/documents in the bid to be
true and correct.
10. The e-tenders should be submitted online till 27-01-2016 upto
5:00 pm and shall be opened on 286-01-2016 at 11:00 am.
11. The e-tender must be accompanied with earnest money amounting Rs.
500/- (online payment) as per e- tendering procedure.
12. Tenderers are also required to submit a hard copy of this tender
on or before the closing date 27-01-2016 upto 5:00 pm at the office
of the under signed i.e. Directorate, Animal Husbandry, Punjab
17-Bays Building, Sector-17, Chandigarh.
13. The undersigned reserves the right to accept or reject one or
all offers/tenders and holds the discretion to increase/decrease the
quantity of any or all the items. The undersigned also hold the
discretion to place the order for any or none of the items
qualifying in the tender and may increase/decrease the quantity of
any or all the items as per requirement of the Department
14. Successful tenderers will have to submit a Security deposit of
10 % of the ordered value within the stipulated period of time after
issuance of orders.
15. For participating in the above e-tender, the bidders shall have
to get themselves registered with
http://etender.punjabgovt.gov.in
and get user ID & password. The bidders who have not registered with
e-procurement portal need to get registered by paying the requisite
registration fee for e-tender participation and obtain Class 3
Digital Signature Certificate (DSC) which are mandatory to
participate in the e-tendering process. For any
clarification/difficulty regarding e-tendering Process please
contact on helpdesk numbers 09257209340, 08054628821, 0172-3934667.
16. The contractors/ tenderers / bidders are also required to pay
tender processing charges of Rs. 2,280/- or an estimated amount as
per tender which are to be deposited online. (This tender processing
fee/charges are other than the firm registration amount for Digital
Signature Certificate DSC).
17. e-Tender details can also be obtained from the Departmental
website
www.husbandrypunjab.org.
FAX No:
0172-2701832
Director Animal Husbandry,
Telephone No.
0172-2701324
Punjab, Chandigarh.
Website www.husbandrypunjab.org
Tendering
Procedure.
It will be
a two stage tendering. The technical tenders and
financial/commercial tenders will have to be submitted AS
PER E
-TENDERING PROCEDURE.
The Technical Bids should contained detail
information on the following: -
-
Nature of Ownership.
-
Composition of the Firm.
-
Bankers Name & Address.
-
Annual Turnover of last five years.
-
C.S.T/S.T No./Vat No.
-
PAN/TAN No.
-
Tax clearance.
-
Whether Manufacturer/Sole Selling
Agent/Distributor/Authorized Dealer.
-
Experience in line.
-
Capability/Capacity to service the requirement.
-
Details of relevant infrastructure.
-
Arrangements of after sale service.
-
List of Clients.
-
Quality Assurance/Monitoring system followed.
Certificates where needed should be attached
duly attested.
Financial/Commercial Bids.
Financial Bid should contain the price
quoted per unit. The following information should be clearly given
in the Financial Bid:-
-
Price per Unit.
-
Place of Delivery.
-
Status of Taxation/Duties etc.
-
Lead time/Delivery Period.
-
Packing & forwarding.
-
Mode of Transportation.
-
Payment condition.
-
Warranty/Guarantee.
-
Validity of Offer.
-
Acceptance of Terms of N.I.T.
-
Details of Earnest money attached.
Financial Bids will be opened only of those
tenderers, who qualify and are found suitable during the processing
of Technical Bids.
TERMS AND CONDITIONS
1.
Tender should have satisfactorily completed two similar type
of quoted work related to Vaccine Production/ /Quality Control/
Animal House during the last ten years. The firm who executed the
work of more than 75% of the project cost will be eligible . At
least one same nature work completed should be of Central/State
Government Organization /Central autonomous bodies/Central Public
Sector undertaking.
2.
Rates should be quoted in Indian Rupees only, FOR anywhere in
Punjab/Chandigarh.
3.
All applicable taxes should be included in the quote.
4.
Brochure/leaflets/catalogues for the completed projects
should be submitted alongwithtender.
5.
Trouble free performance of the project for a minimum period
of two years from date of commissioning should be guaranteed . Any
defect intimated should be attended to and rectified within 15 days
of receipt of such communication within guarantee period. The
guarantee shall include cost of spares and labour.
6.
The supplier should give an undertaking that they will be
responsible to carry out the preventive maintenance and to repair
the equipment during guarantee and post guarantee period.
7.
The product offered should be supported with AMC for next
three years on expiry of the guarantee period. Full details of
after sale service offered during the post guarantee period should
be furnished alongwith tender specified.
8.
Information of actual completed projects in India supported
with evidences and performances should be furnished alongwithtender.
9.
Tenderers should submit complete power point presentation on
the organization, experience of work, man power with financial
details.
10.
The supplier shall train to the satisfaction of the purchaser
one or two technicians at site/factory for operating, servicing and
undertaking minor repairs without extra cost.
Supplier will have to deposit 10% value of the
total price of the items in the form of Demand Draft/FDR payable at
Chandigarh in the name of Director, Animal Husbandry, Punjab,
Chandigarh within 10 days of receipt of supply order as security
money.
Detailed specifications regarding upgradation of
Punjab Veterinary Vaccine Institute, Ludhiana for Quality Control-BOQ
A. HVAC Systems
1. Air Condensing Units (Carrier/ETA/Blue Star/Hitachi/Voltas)
Supply and installation and commissioning of air cooled condensing
units with scroll type compressor complete with copper piping, R-22
refrigerant gas, HP and LP cutouts, control cabling etc.
Thermostatic expansion valves/capillary tubes, thermostats for
tripping the compressors after reaching the temperature in
conditioned areas and with insulation of the suction line. Air
cooled condensing coil with fan and motor along with angle frame for
mounting the unit on the terrace.
(a)
Capacity: 5.5 TR
------ 1 No.
(b)
Capacity: 7.5 TR
------ 1 No.
The
inner connecting piping should be carried out accordingly.
2. Air handling units (Edge Tech/Systemair/Strides/VTS/Zeco/Chempharma)
Supply, installation, testing & commissioning the AHU’s as per
specification including all accessories as specified and as required
Belt driven Centrifugal fans with motor and starter panel with all
necessary connections with Service Doors and cabling to be
included. All AHU’s will be given only one power input cable. Any
looping should be done by OEM in case of multiple motors in one AHU.
Pre plasticized
Sheet/powder coated, Extruded Aluminiumpanta post frame work. Fan
Section, coil section, filter section, with necessary insulations,
drain pan etc. Cooling coil of copper tubes and aluminium fins
(min. 10fins per inch) and required number of rows deep.TEFC sq.
cage induction motor of required rating including mounting and
fixing arrangements.Centrifugal Fans.Anti vibration springs/
isolator bearings etc. To include 50mm thick synthetic media filter
with frame. 90% efficiency down to 20 micron.To include Fine Filter
of 99.9% efficiency down to 5 micron.To include Hepa Filter of 99.9%
efficiency down to 0.3 Micron. Insulation of all section with fire
retardant insulation material as per manufacturers standard. Air
vent on cooling coil with globe valve/screwed plugs. Insulation of
Drain pan as per specifications. Double canvas connections of fire
retardant quality for connecting AHU’s to ducting/plenum. Insulated
drain piping with trap till the outlet of the AHU. Duct damper
while AHU is OFF with relays etc. Includinjg R.C.C. foundation
along with PCC/RCC sub base with bolts and nuts and finishing the
slabs or any opening etc. good as same Limit switch in door and
inspection lamps to be fixed Lockable off push button to be provided
near AHU if machine is 3mtrs and above far from respective panel
board to be included in the AHU cost.
(a)
AHU
1 of capacity 2913 CFM at 125mm WG SP, with 1. of 5.5 TR
Cooling Coil and
respective interconnecting pipe with all accessories.
------ 1 No.
(b)
AHU
2 of capacity 3037 CFM at 125mm WG SP, with 1 No. of 7.5 TR
Cooling Coil and
respective interconnecting pipe with all accessories.
------ 1 No.
3. Ventilation air handling units (Edge Tech/Systemair/Air Flow/Zeco/
Chempharma)
Supply, installation & commissioning of double skin, horizontal
ventilation unit constructed out of 24 G precoated GI sheet as outer
skin, 24G plain GI sheet as inner skin with 23+/-2mm thickness PUF
section of density 36+/-22 Kg/m3 in between and comprising of
following sections: Provision to fix 50mm thick pre filter (Merv-8)
Fan section with DIDW forward curved fan, motor V-belt & drives
set. Manually operated supply air damper.
(a)
VUS-1 of capacity 600 Cfm at 75mm WG
SP -------
No. 1
4. Exhaust handling unit (ZielAbegg/Kruger/Nicotra)
Supply, installation & commissioning of DOUBLE SKIN HORIZONTAL
FLOOR MOUNTED EXHAUST UNITS. Provision to fix 50mm thick pre filter
(Merv-8). Fan Section with DIDW forward curved fan, motor, V-belt &
drives set. Manually operated supply air damper.
(a)
VUE-1 of capacity
600 Cfm at 65mm WG
SP ------- No.
1
Cabinet fan for clean room AHU 1 to 6 for exhaust of return air with
capacity below (Chempharma/GMP technical solutions of equivalent)
Direct driven cabinet fan with forward curve double inlet impeller.
The casing is made of galvanized steel. The impeller shall be anti
vibration rubber pads and its outlet connected with casing through a
canvas joint.
(a)
Capacity 900 Cfm
------ No. 2
(b)
Capacity 600 Cfm
------ No. 4
5. STRIP HEATERS
Supply, install, testing & commissioning of strip heaters
comprising thermostat, humiditistat, safety thermostat,
contractors. Minimum capacity of strip heaters Shall be 3KW
(a)
Duct mounted strip heater capacity of 4.5 kw for AHU
1 ------- 1 No.
(b)
Duct mounted strip heater capacity of 3.0 kw for AHU
2 ------- 1 No.
6. Room Air Conditioning Units (Carrier ETA/ Blue
Star/Hitachi/Voltas)
------Nos. 2
Supply & installation of split air conditioning system complete with
indoor &Outdoor unit & interconnecting copper piping, insulation &
other accessories. Outdoor unit will have weather proof isolator and
indoor unit will be operational With remote control. All necessary
Electrical switch connection shall be provided by the Vendor- 1.5
TR.
7. Ducting (Edge Tech/Systemair/Strides/VTS/Zeco/Chempharma)
Supply, Fabrication and installation of PAL Pre insulated ducts
(FACTORY FABRICATED SHEETS) in accordance with the approved shop
drawingsComplete with all accessories like flanges,
suspension rods, wire hanger,Anchor bolts, GI bolts & nuts etc., as
required by the specifications.
(a)
30mm Thick upto 1000mm width without internal supports *(equi. To
24G) ------ SQM500
(b)
20mm Thick from
1501 mm to 2200 width without internal supports *(equi. To 20G) —SQM
80
8. Mechanical Supports (Ajantha/Systemair/Dynacraft/Chempharma/GMP
Technical Solutions)
(a)
Supply, Fabrication and installation structural supports made out of
Channel/Pipe for Duct Support, Equipment Support for all the Air
conditioning equipments ----Ton 4
(b)
PUF
sandwiched Aluminiun pane of 50 mm thick with pre painted sheets of
0.5 mm on both sides for canopy construction
---Sqm 60
9. Supply Air Module (Ajantha/Systemair/Dynacraft/Chempharma/GMP
Technical Solutions)
Supply
Installation testing and commissioining of (Factory Fabricatedd )
HepafilterofEffieciency 99.9 % down to 0.3 microns in filter plenum
of 18G with rubber gasket in SS suitable frame work with 70%
perforated ss grille, with gear operated Volume Control damper, DOP
port, pressure sensing port etc. The HEPA filters will be fixed to
the plenum using M6 SS rode ,304 Q type SS bolts and nuts).
SS perforated
sheets Mat finish .Hole size 23mm x 7mm oblong shape with 70%
perforation.
610X350X350 mm
---- 17 Nos.
10. Return Air Grills (Ajantha/Systemair/Dynacraft/Chempharma/GMP
Technical Solutions)
Supply and
installation of Return air grill in aluminium extruded / GI powder
coated construction with GI powder coated damper
arrangement. 400x100
mm
------- 27 Nos.
11. Supply Air Grills/diffusers (Ajantha/Systemair/Dynacraft/Chempharma/
GMP Technical Solutions)
Supply of
aluminium extruded/GI powder coated supply air grills/diffusers with
Damper arrangement for
control
(a)
300mm X
300mm
------Nos. 4
12. Exhaust Air Grills/diffusers (Ajantha/Systemair/Dynacraft/Chempharma/
GMPTechnical Solutions)
Supply and
installation of exhaut air grill in aluminium extruded/GI powder
coated constructed with GI powder coated Damper
arrangement.
(a)
300mm X
300mm
------Nos4
13. Fire damper (Ajantha/Systemair/Dynacraft/Chempharma/GMP
Technical
Solutions)
Supply and installation of fusible link type fire damper suitable
for being mounted
on the supply
stream.
------SQM 2
14. Volume Control Damper (Air Flow/Carrier/Blue Star/Chempharma)
Supply and installation of VCD’s with GI powder coated damper
suitable to
be mounted in the
duct
branches.
------SQM 8
15. Magnaulicguages (Pressure indicator) (H Guru/Waree/Dwyer/Chempharma)
Supply and installation and commissioning of pressure monitoring,
magnaulic
Guages range 0-10mm with complete fittings and pressure piping
connectors
and
necessary accessories with Magnehaulicguage should be housed in a SS
304
box
construction
--- Nos. 15
16. Temp & RH indicators (Waree/Dwyer/HTA)
Supply installation and commissioning of temperature & RH indicators
In
the
rooms.
----Nos. 15
17. Testing, Commissioning, Validation & Documentation charges
DQ/IQ/OQ/PQ
documents, Maintenance manual, calibrated Test certificates
for
the following equipments. The following tests to be done at rest
and operation
of
clean room.
(1)
Smoke test
(2)
All
balancing and velocity profile test
(3)
Pressure
balancing
test
--- 1 No.
(4)
Particle Count Test
(5)
Temperature & RH test
(6)
Filter integrity test
(7)
Air
Flow Pattern &
(8)
VOC
Test
(C) Electrical Systems (CPRI Approved Contractor)
18.
Electrical Panel (Finolex/Kapp/Win Cable/RR Cable/Havells)
Supply, installation, testing and commissioning of extensible type,
cubical MCC
panel comprising
of switch fuse units, busbar, cable alley, fabricated from 2mm
thick CRCA sheets
duly rust inhibited and stove enamel painted complete with
heavy duty rubber
gaskets, hinged compartment doors, removable gland plate
for cable entry,
sheet steel or 5mm thick compartment segregation, name
plate, -----1 No.
interconnectionbusbar, mounting channels, ammeter, vollmeter of
suitable
range etc.
including fully automatic star delta/DOL starters. Control wiring,
interlocks, push
buttons, indication lamps etc. for the outgoing shall be included
in this panel.
Note: Electrical
Control panel should be made exclusively for all HVAC related
Equipmentsas
listed in the vendors scope.
Contractor to get
the approval for the SLD drawing before panel fabrication and
assembly.
19. Lighting Panel
Supply,
installation of the lighting distribution board DB Panel
-1 ---- No. 1
20. Cables (Finolex/Kapp/Win Cable/RR Cable/Havells)
Supply installation of cables, Laying, fixing testing commissioning
of 1100V
grade
PVC insulated PVC sheated Al/Cu conductor, armoured cables laid in
built
up trenches, cable trays, cleated to wall, including supply of
clamps, ---- No. 1
cleats, spacers, hardware, PVC conduits etc., all of zinc coated
iron but
excluding supply fabrication and panning of structural steel and
excavation
of
earth.
21. Cable and terminations (Finolex/Kapp/Win Cable/RR Cable/Havells)
Supply and installation of end terminators and connections, Armoured
cables
with
double compression brass cable glands and crimping type lugs
including
supply of glands and lugs, ferrules, insulation tape etc. Fixing of
colored
ferrules on individual cores, dressing of cables etc. Lugs shall be
heavy duty ----- No. 1
long
barrel type.
22. Cable tray (Finolex/Kapp/Win Cable/RR Cable/Havells)
Supply and installation of trays, constrtucted out of 2mm thick GI
including
the angle iron
supports in wall/ceiling/structure etc. complete with GI
hardware ----- No. 1
23. Earthing
Supply installation of earth pits, along with earth stations, earth
plates and
earth
conductor
----- No. 1
24. Point Wiring
Supply and
installation of wiring for lighting with 1' dia , 1.5mm thick PVC
----- Nos. 30
conduits , using 1.5 sqmm PVC insulated multi strand copper wires
for phase ,
neutral and earth with modular type switches & sockets of 5/ 15/ 32A
and all
accessories for Clean Room Equipments and Lightings in
clean room area.
(D) Clean room finishes and accessories
25. Modular Wall panel (Clear Air/Chempharma/GMP Technical
Solutions)
Supply and
Installation of wall panel 100mm thick made of powder coated GI
---- SQM 220
sheet
of 0.8mm thick on both sides with EPS 16kg/M3 density
sandwitched
between sheets including bottom runner, interconnecting profiles,
fixing
arrangements with
silicon sealant and other accessories with necessary return
air risers
wherever required
26.
Walkable false ceiling Panel(Clear
Air/Chempharma/GMP Technical Solutions/ SRP)
Walkable false ceiling with powder coated GI sheet of 0.8mm thick on
both side ----- SQM 130
80mm
thick panel with 18 Kg/m3 density PUF sandwitched between sheets
including hanging arrangements, wall cutouts for lights and filters
and ceiling
with
silicon sealant after fittment.
27. View Panels(Clear Air/Chempharma/GMP Technical
Solutions)
Supply and Installation double glazed view panel made of Powder
coated GI -----Nos. 8
Construction with 5mm thick float glass duly finished with wall
panel including
accessories like silicon sealant , double adhesive tapes
etc. Size : 600mm x 600mm.
28.
Coving(Clear
Air/Chempharma/GMP Technical Solutions)
Supply and Installation of Aluminium powder coated or anodized
polished corner -----mtr 400
R15
coving.
29. Corner (Clear Air/Chempharma/GMP Technical Solutions)
3 D Corner pieces
with Aluminium die casting material with duly powder coated ----
Nos. 100
to match with the
coving in the floor and walls.
30. Light Fixtures
Supply and
Installation of surface mounted CFL fixtures for entire area
2 x 36 Watts CFL
Type : 2' x
2'
---- Nos. 13
2 x 18 Watts CFL
Type : 1' x
1'
----- Nos 4
31. Doors(Clear
Air/Chempharma/GMP Technical Solutions / SRP)
a) Modular
sandwiched doors with both side GI powder coated sheet construction
of 0.8 mm thickness , with 45mm thick EPS insulation sandwiched
between sheets , including flushed hinges , view panels , SS304
handles , push plate , suitable gasket for sealing and provision for
door interlocking
Sheet thickness : 0.8 mm
Insulation : EPS
Frame : Powder coated GI
Hinges : SS Butt hinges
Handle : SS " D" type single side handle
Door view panel : 450 X 600 mm
Sealant : silicon
Finish GI Sheet : Powder coated 80 microns
(i)
Single Leaf Door :3 feet X 7
feet ----- Nos
7
(ii)
Single Leaf Door :2 feet 6 inches X 7
feet
----- Nos 8
(iii)
Double Leaf Door 5 feet X 7
feet
----- Nos 2
b)
Double Glazed
View panels made of Powder coated Aluminium sections with 5mm thick
float glass. Wall cut out to be provided by Civil.
View Panel : 6
feet X 6 feet 6"
32. Emergency door(Clear
Air/Chempharma/GMP Technical Solutions)
Supply and
installation of emergency modular sandwiched doors with both side
powder coated GI
sheet construction 0.8 mm thickness duly flushed with the
walls , with 45
mm thick EPS, insulation sandwiched between sheets with panic---
Nos. 1
bar with single
point locking , latch and keep plates , handle and door frame ,
including flushed
hinges , view panels , SS304 handle , push plates and hydraulic
door closers
(5'X7')
33.
Access Door Control System(Clear
Air/Chempharma/GMP Technical Solutions)
-----Nos. 2
Access control
system is to designed to control the Automatic entry/exit control
system for authorized personnel using a smart card to control the
entry into the selected areas and manage movement of people by
defining access permissions based on the area, time of each user and
maintaining a log of all the events.
Components of an access control system:
Software:
Used to adjust all parameters of the system, control hardware,
display events related to
movement of users, alarms, and operation of hardware devices. The
software is also used for storing all events in the database and
generating reports based on requirements defined by an operator.
Electromechanical hardware:
·
Electric locks
·
Turnstiles
Electronic hardware:
·
Controllers: receive settings from software and control the
electromechanical hardware of the system.
·
Contactless readers: read unique numbers of identification
cards/tags and forwards the numbers tocontrollers.
·
Fingerprint readers: scan fingerprint images, compare them with the
templates stored in the internal
·
reader database (or on a smart card) and send the verification
results to controllers.
System users:
·
Operators: responsible for administrating the system, creating new
users, issuing cards and
·
performing other regular daily tasks.
·
Installers: responsible for installing, programming, maintaining and
troubleshooting the system.
·
Users: regular staff of the company, with permanent or long-term ID
cards (or PINs), who use the
·
system to gain access to certain building areas as configured by
operators.
·
Visitors: people that are not employed by the end-user company, but
still have rights to access certain
·
areas (contractors, visitors, delivery people, etc.).
Technical requirements
A.
Software
1. There shall be no limitations on the number of PC workstations,
readers and alarm inputs.
2. The number of cards/users shall be limited only by memory
available in hardware.
3. At least 3 active cards per user shall be supported.
4. At least 8 access levels per user shall be supported.
5. Access levels should be assigned to a user, not to a card, in
order to help issue a new card in a
fast and easy manner, without reassigning access levels.
6. The software shall have the ability to produce the following
report types: system and alarm
event reports, user reports, hardware configuration settings, access
level reports, employee time & attendance reports.
7. The software shall support an unlimited number of building floor
plans.
8. Floor plan viewing interface shall have convenient zoom in/out
controls by mouse wheel.
9. The software shall allow operator to conveniently edit floor
plans by “dragging and dropping”
hardware devices to selected plan areas.
10. The software shall be available in the official language(s) of
the country where it is being installed. If such language is not
included in the standard installation, the software shall support
user friendly translation method: simply replacing program text
directly in the software (“on the fly”), without the need of sending
any files to the manufacturer for compiling.
11. The software shall have a modern interface, attractively
designed and convenient to use.
12. The software shall be adapted for operators who have not
received any special training related
to management of integrated security systems. Graphical user
interface shall be intuitive. Introducing the system to a new
operator shall not take more than 1 hour.
13. In order to reduce the amount of work done by an operator, the
software shall incorporate an
option to copy objects: users, doors, floor plans, time schedules,
access levels and holidays.
14. The software shall store information and provide reports about
visitors and appointments.
B.
Hardware
1. Two-door controller shall have the following inputs and
outputs:
i. Power output for two readers
ii. Outputs for controlling LEDs and beepers of the readers
iii. TwoWiegand or Clock/Data inputs
iv. Two exit button inputs
v. Two door contact inputs
vi. Two auxiliary alarm inputs
vii. Tamper input
viii. Inputs for monitoring AC power and backup battery state. There
should be an option
to reconfigure these inputs to function as general purpose inputs.
ix. Two relays for controlling an electric lock.
x. Two general purpose auxiliary output relays.

34. Garment cubicle(Clear Air/Chempharma/GMP Technical
Solutions/ Yorco/ SRP)
------Nos. 4
Supply &
Installation of garment cubicle 1200 mm wide , for storing 12
garments , unit made out of PCGI, fitted with hangars , Flourscent
lights , UV lights , Switches for lights , front glass sliding doors
etc
35. Cross over Bench (Clear Air/Chempharma/GMP Technical
Solutions /Yorco/ SRP)
-----Nos. 2
Supply &
Installation of Cross over bench made out of SS 304 , size 1000 mmX
400mm X 550mm [Double side]
36.
Dynamic pass box(Clear
Air/Chempharma/GMP Technical Solutions/ Yorco)
----- Nos. 3
Supply
installation of dynamic pass box made out of GI powder coated unit
fitted with lighting , electronic interlocks , ss bottom surface .
Internal dimension : 610 mm W X 610 mm D X 610 mm H External
Dimension : 730 mm W X 690 mm D X 790 mm H
37. Bio Safety cabinets unit
(Clear Air/Chempharma/GMP Technicals
/Klenzaid/ Yorco/ SRP)
---Nos. 2
Bio safety
Cabinets Unit, Type A2 meeting BSF Cabinet &amercian NSF/ ANSI 49
with zero recirculation and zero exhaust system. Made of SS 304
inside and Powder coated GI outside frame.Size : 6' x 2' x 3'
38. Horizontal laminar Air flow unit(Clear
Air/Yorco/SRP/GMP Technical Solution /Klenzaid/ Thermadyne)
---Nos. 2
Laminar Air Flow
Unit with Inlet and Outlet Chamber made of SS, fitted with HEPA
filter with efficiency 99.9% down to 0.3 micron. Comprising of UV
lamp for sterlization, acrylic sliding front door.Fitted with
Manometer for HEPA filter choking system and cock for Gas
connection.
39. Aluminum Grid false
ceiling ----SQM 100
600 x 600mm
Aluminium T Grid False Ceiling Frame complete with suitable
adjustable hanger supports anchored on the slab and PVC laminated
Gypsum boards with cutouts and lights/grills/ diffusers fixing
arrangement.
40.
Epoxy
flooring
---SQM 130
Self Levelling
type 3mm thick Epoxy flooring. Primer to be applied before laying of
Epoxy.
Shell Structure of the Quality Control Lab at the Punjab Veterinary
Vaccine institute, Ludhiana is being constructed by PWD wing
of Panchayati Raj. The eligible contractor will coordinate with
the construction company for earlier execution of the work .
During the execution of work, technical aspects will be examined
by the technical committee of the Department , whose technical
directions has to be adopted .
Note :
Detailed Drawings of Quality Control Lab (Line Plan/ Shell
Structure) can be procured from
the office of Deputy Director, Animal Husbandry,
Punjab Veterinary Vaccine Institute,
Ludhiana . Contact no. at the site is as
follows: Office – (0161-2401499)
Mobile – 098883-16728